8-2
8. ACTUAL OPERATON
8.1.2 Zero Adjustment Using BT200
Display Description
Call up the menu panel and select “C:ADJUST” with the arrow key.
Press ENTER key to call up the panel displaying the parameter
subitems.
Confirm the inverse video bar is on “C01:ZERO TUNING”.
Press ENTER key to call up the data setup panel and select
ENABLE”.
Press the ENTER key to set the data and return to the parameter sub
items panel. Select “C02:MAGFLOW ZERO”with the arrow key.
Pressing the ENTER key causes the data setup panel to be displayed.
While “C02:MAGFLOW ZERO” is displayed, press the ENTER
key twice at an interval of a few seconds.
Then, “AUTO ZERO” is now displayed.
After about 20 seconds, pressing the “F4” [OK] of the function key
causes the menu panel to be displayed. The zero correction is
displayed. Then the panel returns to data display mode.
MENU
A: DISPLAY
B: SET
C: ADJUST
D: DISP SEL
E: TOTAL SET
F: PULSE SET
HOME SET ADJ ESC
ENTER
PARAM
C01: ZERO TUNING
ENABLE
C02: MAGFLOW ZERO
0.05
C60: SELF CHECK
GOOD
DATA DIAG ESC
PARAM
C01: ZERO TUNING
INHIBIT
C02: MAGFLOW ZERO
0.05
C60: SELF CHECK
GOOD
DATA DIAG ESC
SET
C01: ZERO TUNING
ENABLE
SET
C02: MAGFLOW ZERO
0.05
+00.05
CLR ESC
SET
C02: MAGFLOW ZERO
AUTOZERO
FEED NO OK
PARAM
C01: ZERO TUNING
ENABLE
C02: MAGFLOW ZERO
0.02
C60: SELF CHECK
GOOD
DATA DIAG ESC
ENTER
ENTER
ENTER