IM 1E10C1-E
7-19
7. OPERATION VIA HART COMMUNICATOR
ADMAG SE :
Setting fld dev
output to 4mA
HELP SAVE ABORT OK
8
9
ADMAG SE :
Enter meter value
1.000000
1.000000
DEL DEL ABORT ENTER
F4
VWX
2
(ENTER)
10
ADMAG SE :
Scaled output: 1.000
equal readout
device?
1 Yes
2 No
DEL DEL ABORT ENTER
F4
(ENTER)
ADMAG SE :
Trim will be scaled
from 4.000 to 20.000
1 Proceed
2 Change
HELP SAVE ABORT ENTER
3
4
Select “Change”, and press ENTER (F4).
The same operations as for “D/A trim” are required when
selecting “Proceed”.
Enter the read value on the meter when the signal is 4 mA. In
this case, enter the value of the voltage across a 250Ω resistor
(1 V), and press ENTER (F4).
Enter the read value on the meter when the signal is 20 mA.
Then, enter “5” (5 V), and press ENTER (F4).
Select “Proceed” and press ENTER (F4).
Connect the voltmeter, and press OK (F4).
Press OK (F4). The output signal of 0% is output.
Voltmeter reading: 1.010
Enter the reading of the voltmeter (1.010), and press ENTER
(F4).
(The output of the ADMAG SE changes.)
Voltmeter reading: 1.000
Because the reading on the voltmeter is 1.000, select “Yes” and
press ENTER (F4).
If the reading is not 1.000, select “No”.
Repeat step until the voltmeter reads 1.000 V.
ADMAG SE :
Set scale- Hi output
value
20.000000
20.000000
HELP DEL ABORT ENTER
5
ADMAG SE :
Set scale- Lo output
value
4.000000
4.000000
HELP DEL ABORT ENTER
ADMAG SE :
Trim will be scaled
from 1.000 to 5.000
1 Proceed
2 Change
DEL DEL ABORT ENTER
6
7
ADMAG SE :
Connect reference
meter
HELP DEL ABORT OK
‘1’
‘1.01’
F4
(ENTER)
‘5’
F4
(ENTER)
F4
(ENTER)
F4
(OK)
F4
(OK)
9