Yokogawa DAQWORX Instrukcja Użytkownika Strona 169

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 336
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 168
6-42
IM WX104-01E
Alarm action
No Logging
Select [ON] to hide alarm indication. The [Detect] setting is enabled in the Measure
channel, Math channel, Ext channel tab(s).
This function disables the alarm indicator and the logging of alarm events to the alarm
summary. It also disables the display of alarms by the alarm annunciator (release
number 3 or later).
Annunciator mode and Sequence (Release number 3 or later)
To use the annunciator function, select [ON] and set the sequence.
Settings Description
ISA-A-4 A no lock-in sequence.
ISA-A A lock-in sequence.
ISA-M A double lock-in sequence.
Time off color (Release number 3 or later)
The annunciator window display color when no alarms are activated. You can select
[White] or [Green].
Alarm display (Release number 3 or later)
Level
When multiple alarms occur, the DX gives higher priority to the display of alarms with
higher levels.
Settings Description
1>2>3>4 The order of alarm level preference, from highest to lowest preference, is 1, 2,
3, 4.
1>4>2>3 The order of alarm level preference, from highest to lowest preference, is 1, 4,
2, 3.
1>4>3>2 The order of alarm level preference, from highest to lowest preference, is 1, 4,
3, 2.
Alarm 1, Alarm 2, Alarm 3, and Alarm 4
You can set the alarm color for each alarm level. It is easy to understand what
processes are taking place when alarms occur if you associate an alarm’s color with
its level. This setting applies to all channels.
6.5 Entering Basic Settings
Przeglądanie stron 168
1 2 ... 164 165 166 167 168 169 170 171 172 173 174 ... 335 336

Komentarze do niniejszej Instrukcji