Yokogawa Value Series FX1000 Instrukcja Użytkownika Strona 54

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 206
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 53
1-46
IM 04L21B01-17EN
Writing Measured Values to the Server
Example
Write the measured value (16-bit signed integer) from channel 001 to register 40001
of instrument A.
16-bit signed integer
Measurement channel
Register of instrument A
001 40001
Command setting
W 001 - 001 1 40001 INT16
Writing Computed Values to the Server
Example
Write the computed values (32-bit signed integers) from channel 101 to registers
40001 and 40002 of instrument A, in the order lower 16 bits/higher 16 bits. Only the
smallest register number need be specified in commands.
32-bit signed integer
Computation channel
Register of instrument A
40001
40002
101
lower bytes
higher bytes
Command setting
W-M 101 - 101 1 40001 INT32_L
1.10 Using Modbus to Read Data From and Write Data to Other Devices
Przeglądanie stron 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 205 206

Komentarze do niniejszej Instrukcji

Brak uwag