Measurement Channels and Alarms
3-13
IM 04L42B01-01E
1
2
3
4
5
6
7
8
9
10
11
12
13
App
Index
Setup Items
First-CH/Last-CH
Select the target channels. The target channels are common with the other items that
are displayed on the screen.
Alarm > 1, 2, 3, and 4
For each alarm, 1 to 4, select On to enable it.
Alarm > Type
Select the alarm type.
Settings Name Description
H High limit alarm
L Low limit alarm
h Difference high limit alarm Can be specified on channels set to difference computation.
l Difference low limit alarm Can be specified on channels set to difference computation.
R
High limit on rate-of-change alarm
r
Low limit on rate-of-change alarm
T Delay high limit alarm
t Delay low limit alarm
Alarms on channels set to difference computation are inserted at the following
positions.
Input value
Measured value on the reference channel
H, L, T, t R, r, h, l
Measured value
Alarm > Value
Set the alarm value for the selected alarm type.
When the Mode of the Channel Is Set to Volt, TC, RTD, or DI
Type Value Example of a Range of Alarm Values
H, L Value in the measurable range –2.0000 to 2.0000 V for 2 V range
R, r 1 digit to the upper limit of the width of
the measurable range
0.0001 to 3.0000 V for 2 V range
However, less than or equal to 30000
excluding the decimal point.
0.1 to 1760.0°C for thermocouple type R
T, t Same as H and L. Same as H and L.
When the Mode of the Channel Is Set to Delta
Type Value Example of a Range of Alarm Values
H, L Value in the measurable range –2.0000 to 2.0000 V for 2 V range
h, l Value in the measurable range –1760.0 to 1760.0°C for thermocouple type R
R, r 1 digit to the width of the measurable
range
0.0001 to 3.0000 V for 2 V range
However, less than or equal to 30000
excluding the decimal point.
0.1 to 1760.0°C for thermocouple type R
T, t Same as H and L. Same as H and L.
When the Mode of the Channel Is Set to Scale, Sqrt, or 1-5V
Type Value Example of a Range of Alarm Values
H, L –5% to 105% of the scale width.
However, within –30000 to 30000
excluding the decimal point.
–5.0 to 105.0 when the scale is 0.0 to 100.0
–120.00 to 300.00 when the scale is –100.00
to 300.00
R, r Within 1 to 30000 excluding the decimal
point.
0.1 to 3000.0 when the scale is 0.0 to 100.0
0.01 to 300.00 when the scale is –100.00 to
300.00
T, t Same as H and L. Same as H and L.
3.7 Setting Alarms on Channels
Przeglądanie stron 108
1 2 ... 104 105 106 107 108 109 110 111 112 113 114 ... 358 359

Komentarze do niniejszej Instrukcji

Brak uwag