IM MW100-S16E-1
Ed01
Table 23. Parameters for configuring data variation
Kind Configuration
Default Variation Default variation to reply to the request with variation 0
- In case of Binary Input, Binary Output objects, selectable from :
- 1 (Packed Bit)
- 2 (Flag)
- In case of Analog Input objects, selectable from :
- 1 (Int 32 with Flag)
- 2 (Int 16 with Flag)
- 3 (Int 32)
- 4 (Int 16)
- 5 (Short Float with Flag)
- 6 (Long Float with Flag)
- In case of Analog Output objects, selectable from :
- 1 (Int 32 with Flag)
- 2 (Int 16 with Flag)
- 3 (Short Float with Flag)
- 4 (Long Float with Flag)
Timestamp Enabling switch for putting timestamp into event data
- toggle switch to "Put" or not
Relative Time Enabling switch for using relative time as timestamp
- toggle switch to "use" or not