3-12
IM MW100-01E
Modbus Client Setting 2
Register the server to which commands are sent. Use the number of the registered
server for Modbus client setting 3.
1.
From the Top screen, click Communication Setting > Modbus Client Setting 2.
The server list is displayed.
2.
Enter the server name in the Server box.
3.
Enter the server port number in the Port box.
4.
Click the Apply button. The setting changes take effect.
Modbus Client Setting 3
1.
From the Top screen, click Communication Setting > Modbus Client Setting 3.
2.
Enter settings in the same manner as for Modbus Master Setting 2. Enter the
server number of the server list in the Server box.
3.
Enter the server unit number in the Unit box.
For details on the registers and data types, see “Modbus Client Function” under “Modbus
Protocol Specifications” in section 5.2.
3.2 Communication Settings