Select ―Ethernet-Module Generic Ethernet Module‖ from the listing……
Enter the following items:
Name: ―MW100‖
Description: Yokogawa MW100 Data Acquisition Unit (description is optional).
Comm Format: DINT (Note: Once the COMM Format is set, it may not be changed in the future. To change the COMM
Format, the module will need to be deleted and recreated).
Address/Host Name IP Address: 192.168.001.101
Input Assembly Instance:110 (MW100 Measurement Channels), Size: 10 (MW100 Measurement Channels 1 thru 10)
Output Assembly Instance: 130 (MW100 Communication Channels), Size: 6 (MW100 Communication Channels C01
thru C06)
Configuration Assembly Instance: 190, Size: 0