5.2 Error Messages and Their Corrective Actions
Error Messages on the Address Setting Software
Error Code Message Corrective Action/Description Reference Page
- IP address is invalid. Enter the correct IP address. 2-3
- Subnet mask is invalid. Enter the correct subnet mask. 2-3
- Default gateway is invalid. Enter the correct gateway address. 2-3
W5000 Address setting failed. Attempted to change IP address while connection -
established, or MW100 whose setting was attempted to
be changed is connected to other software. Disconnect
the MW100 before changing settings.
Error Messages on the Viewer
Error Code Message Corrective
Action/Description Reference Page
E0004 File write error. The file cannot be created for some reason. -
E0212 Can’t read file. The target file cannot be loaded, or was deleted. 3-2
E3111 Channels of the specified Channels with the specified measurement interval 3-22
recording interval do not exist. do not exist in the conversion of the data format.
Change to the correct setting.
E3114 Sampling data number is over the Attempting to load a file containing 5 million or more 3-2
Viewer display limit of 5 M. data points.
E3120 Not a data file. The file cannot be read, or it is corrupt. 3-2
W3115 Exceeded the range of the Excel Change the range to be converted so that it is within 3-23
sheet. Convert to Excel? the allowed range of Excel.
W3116 Exceeded the range of the Lotus Change the range to be converted such that it lies within 3-23
1-2-3 sheet. Convert to Lotus? the allowable range for Lotus 1-2-3.
Error Messages on the Calibrator
Error Code Message Corrective
Action/Description Reference Page
W4700 Connection failure. The MW100 main unit to connect to is not in Calibration 4-1
Check the IP Address/Host Name. mode. Place the MW100 main unit in Calibration mode.
To change the network settings such as the IP address, 2-1
start the Address Setting software.
W4701 Failed to write the calibrated value. Recalibrate. If the message is still displayed, service 4-4 to 4-11
required.
W4702 Failed to calibrate. Recalibrate. If the message is still displayed, service 4-4 to 4-11
required.