5-2
<Toc> <Ind> <5. MODBUS Communication >
IM 77J01J11-01E 3rd Edition : Oct. 15, 2007-00
5.1.1 Configuration of Message
Messages sent from the higher-level device to the VJ Series consist of the following ele-
ments.
Number of bytes in RTU mode None
Number of bytes in ASCII mode 22
(1) (3) (4) (5)(2) (6)
Element Address
Number
(ADDRESS)
Function CodeStart of
Message Mark
Data Error Check End of
Message Mark
None
1224n
1 1 2n 2
050103E.EPS
(1) Start of Message Mark
This mark indicates the start of a message. Note that only ASCII mode requires a
colon (:).
(2) Address Number (1 to 99)
Address numbers are used by the higher-level device to identify the VJ Series signal
conditioners at the communication destination. (These numbers are identification
numbers specific to individual VJ Series, which are expressed in a hexadecimal in the
message.)
(3) Function Code (See subsection 5.2.1, List of Function Codes)
This element specifies a command (function code) from the higher-level device.
(4) Data
This element specifies D register numbers, the number of D registers, parameter
values, or others in accordance with the function code. (It is expressed in a hexadeci-
mal in the message.)
(5) Error Check
In RTU mode Carried out by the cyclic redundancy check (CRC-16) system.
In ASCII mode Carried out by the longitudinal redundancy check (LRC) system.
(6) End of Message Mark
This mark indicates the end of a message. Note that only ASCII mode requires CR +
LF.