
<Toc> <Ind> <3. PC Link Communication >
3-19
IM 77J04J11-01E 1st Edition : 2006.08.25-00
INF Reads the model, range code number, number of alarms and revision
● Function
Returns the model, range code number, number of alarms and revision of the M Series.
• For the format of response in the event of failure, see subsection 3.1.2.
● Command/Response (for normal operation)
Number of Bytes 1 2 2 1 3 1 2 1 1
44211
Command
element
STX Address
number
(ADR)
CPU
number
01
ChecksumResponse
time (0)
INF 6 ETX CR
Number of Bytes 1 2 2 2 8 8 4 4
Response
element
STX Start register
specified for
readout
refreshing *
Address
number
(ADR)
CPU
number
01
OK 䊐䊐䊐䊐䊐䊐䊐䊐
(Note 1)
Version
Revision
(Note 2)
Number of
registers
specified for
readout
refreshing *
ETX CRStart register
specified for
write
refreshing *
Number of
registers
specified for
write
refreshing *
Checksum
Response (continued)
The * mark indicates fields the FA-M3 UT link module refers to.
Note 1: Model and input/output information of the M Series
Model information
MVHK: Digital limit alarm (DC input type)
MVRK: Digital limit alarm (RTD input type)
MVTK: Digital limit alarm (Thermocouple input type)
Number of alarms
2: 2 points of alarm outputs
4: 4 points of alarm outputs
Range code number
Value set in the parameter IN
Space
Note 2: Version number and revision number
Revision number of downloaded data
ROM version number
.
Komentarze do niniejszej Instrukcji