5. EXPLANATION OF BASIC ITEMS
5.5.2 AI Block Parameters Setup
The AI block outputs the flow rate signals.
There are 4 kinds of submenus as [Batch Information],
[PV Scale], [Output Scale] and [Warning and Alarm]
in the [Analog Input] menu.
Click [Output] [Analog Input] at the Navigation
Tree.
Refer to section 6.3.4 for [Simulation] function.
Figure 5.5.3 Analog Input menu
(1) Calibration range setting
Entry the upper and lower values in the [PV Scale]
submenu.
Figure 5.5.4 PV Scale Setup
(2) Output Scale setting
Entry the flow unit, upper and lower values with their
decimal points in the [Output scale] submenu.
Figure 5.5.5 Output Scale Setup
(3) Fail Safe Mode setting
Entry the fail safe mode, fail scale default value and
output value in the [Analog Input] menu.
Figure 5.5.6 Fail Safe Mode Setup