Step Display Description Text
Ref
6 COUNT
dn
up
The Batch Total counts Up or Down.
Count down from the batch quantity.
Count up from zero.
3.2
7 T OUT The Signal Timeout in seconds.
(Setting to 00 disables this feature.) 3.2.2
8 AOC
En
Dis
Automatic Overrun Compensation.
Note that the Signal Timeout must be greater
than 0 (ie. enabled) for this feature to work.
Enable.
Disable.
3.2.5
9 AUTO R
Off
On
Auto Reset (not displayed if Auto Restart is
programmed - Step 3 above).
Batch Total must be manually reset before
starting the next batch.
The Batch can be automatically reset and
started by pressing only the RUN key.
3.2